HEPA filtration and integrity testing

HEPA filter · Terminal filter · Final filter · Filter leak test

E01 · CLEANROOMS, HVAC AND CONTROLLED ENVIRONMENTSCleanrooms and airChecked against primary sources by SPEQ

The final air filters that make cleanroom air clean, and the installed leak test that shows each one, and its seal, is still intact.

What this page does not claim

An equipment family page teaches how a kind of equipment works and how it is assured. It is not a qualification of any site’s equipment, sets no universal limits, and was checked by SPEQ against the sources it lists, not by an independent engineer.

WHAT IT DOES

A HEPA filter is a "high efficiency particulate air filter specified in accordance with a relevant international standard" (Annex 1, glossary). In a sterile facility the terminal filter, in the ceiling or in a unidirectional airflow unit, is the last barrier between the air handling system and the room.

A filter that met its class at the factory can be damaged in handling, installation or use, or leak at its seal. Annex 1 defines the filter integrity test as one that confirms a filter has kept its retentive properties and "not been damaged during handling, installation or processing" (glossary), and asks for it in qualification (4.25) and in every requalification (4.32).

Where it sits: In the supply air of every classified room, in unidirectional airflow units over grade A, inside isolators and RABS, and in the air supply of depyrogenation tunnels and dry heat ovens.

WHERE YOU FIND IT

  • Cleanroom ceilings and terminal housings
  • Unidirectional airflow units and laminar airflow cabinets
  • Isolators and RABS
  • Depyrogenation tunnels and dry heat ovens (Annex 1, 8.67, 8.70)

In the reference facility: Plant utilities, HVAC & energy centre, Processing & formulation suite, Aseptic filling & isolator line

Not covered on this page: Sterilising-grade liquid and gas filters, which have their own integrity tests; Filter class specifications, which belong to EN 1822 and ISO 29463.

MAJOR COMPONENTS

  • Filter media pack. Captures particles; pleated glass-fibre or membrane media.
  • Frame and seal (gasket or gel). Joins the filter to its housing; a seal leak bypasses good media.
  • Terminal housing or ceiling grid. Holds the filter and provides the upstream challenge and sampling ports.
  • Diffuser or protective screen. Spreads or protects the airflow below the filter face.
  • Pressure-drop gauge across the filter. Shows loading over time; it does not show a leak.

Connects to: Air handling unit and pre-filters upstream; Room or unidirectional airflow zone downstream; Maintenance and filter change procedures; Change control.

INSTRUMENTS AND WHAT THEY MEASURE

  • Aerosol photometer (with aerosol generator). Installed leakage across the filter face and seal, against the upstream challenge. Watch for: upstream challenge not measured or not uniform.
  • Optical particle counter. An alternative leak scan by discrete counting, and room classification downstream. Watch for: sample tubing long or bent enough to lose large particles.
  • Differential pressure transmitter. Pressure drop across the filter, for loading and change decisions. Watch for: ports connected the wrong way round, reversing the sign.
  • Airflow velocity probe (anemometer). Face velocity and uniformity below the filter. Watch for: readings taken at a different height from the one qualified.

PARAMETERS

SETPOINT · MEASURED · LIMIT · ATTRIBUTE
  • Installed filter leakage (limit, % of upstream challenge). Scanned across the face and seal of each installed filter, against the acceptance criterion in the site’s qualified test method.
  • Supply airflow volume (measured, m³/h). At each filter, part of qualification and requalification (Annex 1, 4.25, 4.32).
  • Airflow velocity (measured, m/s). Below the filter face in unidirectional airflow, at the location justified in the qualification protocol (Annex 1, 4.30).
  • Pressure differential (measured, Pa). Across the filter; a rising value shows loading, and the change point is set by the site.

SPEQ publishes no universal alarm or acceptance values: they depend on the process, the product and the site’s own qualification.

CONTROLS, ALARMS AND INTERLOCKS

  • Procedure: Integrity test of final filters at requalification. At most every 6 months for grade A and B areas and every 12 months for C and D (Annex 1, 4.32).
  • Procedure: Tunnel and oven filter tests. Air supplied to a depyrogenation tunnel passes through at least a HEPA filter, with integrity tests at least twice a year (Annex 1, 8.67).
  • Procedure: Change control on filter replacement. A change of final filters is an example of special maintenance that calls for requalification (Annex 1, 4.32).

An alarm asks for a response; an interlock stops an action; a safety function protects people and has its own risk basis.

HOW IT FAILS

  • Pinhole or tear in the media. Unfiltered air enters the room in a narrow jet that a room particle count may miss.
  • Seal or gasket leak. Air bypasses the filter at the frame.
  • Damage during installation or a filter change. A filter that passed at the factory leaks in place.
  • Loading not tracked. Airflow volume falls and pressure differences drift.

ASSURANCE ACROSS THE LIFECYCLE

EXAMPLES, NOT A MANDATORY LIST
  • Supply. Filter class and factory test certificate for each filter.
  • Installation and qualification (Annex 1, 4.25). Installed filter system leakage and integrity test; Airflow volume and velocity; Downstream classification.
  • Requalification (Annex 1, 4.32). Integrity test of final filters; Airflow volume measurement; Air velocity or recovery, as the grade requires.
  • Change. Requalification after a final filter change or other special maintenance.

WHAT THIS DOES NOT PROVE

  • A factory certificate does not prove the filter is intact as installed. Instead: An installed leak scan of the media and the seal.
  • A normal pressure drop across the filter does not prove there is no leak. Instead: The leak scan; pressure drop only shows loading.
  • A passing room particle count does not prove every filter is integral. Instead: Filter-by-filter integrity results.